CN101640424B - On-off system of 1000kV AC ultrahigh-voltage transmission line - Google Patents
On-off system of 1000kV AC ultrahigh-voltage transmission line Download PDFInfo
- Publication number
- CN101640424B CN101640424B CN2009101682558A CN200910168255A CN101640424B CN 101640424 B CN101640424 B CN 101640424B CN 2009101682558 A CN2009101682558 A CN 2009101682558A CN 200910168255 A CN200910168255 A CN 200910168255A CN 101640424 B CN101640424 B CN 101640424B
- Authority
- CN
- China
- Prior art keywords
- uhv
- resistance
- subjected
- circuit breaker
- transmission line
- Prior art date
- Legal status (The legal status is an assumption and is not a legal conclusion. Google has not performed a legal analysis and makes no representation as to the accuracy of the status listed.)
- Active
Links
- 230000005540 biological transmission Effects 0.000 title claims abstract description 84
- 230000005611 electricity Effects 0.000 claims description 3
- 238000006243 chemical reaction Methods 0.000 claims description 2
- 238000011160 research Methods 0.000 description 13
- 238000012360 testing method Methods 0.000 description 13
- 238000005265 energy consumption Methods 0.000 description 10
- 238000000034 method Methods 0.000 description 10
- 238000005516 engineering process Methods 0.000 description 7
- 230000001052 transient effect Effects 0.000 description 7
- 238000009434 installation Methods 0.000 description 6
- 230000008569 process Effects 0.000 description 6
- 238000004088 simulation Methods 0.000 description 6
- 230000000670 limiting effect Effects 0.000 description 5
- 238000010586 diagram Methods 0.000 description 4
- 238000011084 recovery Methods 0.000 description 4
- 238000009413 insulation Methods 0.000 description 3
- 238000004519 manufacturing process Methods 0.000 description 3
- 230000009466 transformation Effects 0.000 description 3
- 230000007774 longterm Effects 0.000 description 2
- 230000000630 rising effect Effects 0.000 description 2
- 238000012546 transfer Methods 0.000 description 2
- 238000004458 analytical method Methods 0.000 description 1
- 238000004364 calculation method Methods 0.000 description 1
- 230000008859 change Effects 0.000 description 1
- 239000003245 coal Substances 0.000 description 1
- 239000004020 conductor Substances 0.000 description 1
- 238000013016 damping Methods 0.000 description 1
- 230000007547 defect Effects 0.000 description 1
- 238000013461 design Methods 0.000 description 1
- 238000011161 development Methods 0.000 description 1
- 230000000694 effects Effects 0.000 description 1
- 230000017525 heat dissipation Effects 0.000 description 1
- 230000007246 mechanism Effects 0.000 description 1
- 230000007704 transition Effects 0.000 description 1
Images
Classifications
-
- H—ELECTRICITY
- H01—ELECTRIC ELEMENTS
- H01H—ELECTRIC SWITCHES; RELAYS; SELECTORS; EMERGENCY PROTECTIVE DEVICES
- H01H33/00—High-tension or heavy-current switches with arc-extinguishing or arc-preventing means
- H01H33/02—Details
- H01H33/04—Means for extinguishing or preventing arc between current-carrying parts
- H01H33/16—Impedances connected with contacts
- H01H33/166—Impedances connected with contacts the impedance being inserted only while closing the switch
Landscapes
- Driving Mechanisms And Operating Circuits Of Arc-Extinguishing High-Tension Switches (AREA)
- Arc-Extinguishing Devices That Are Switches (AREA)
Abstract
Description
技术领域technical field
本发明涉及特高压输电领域,特别是涉及一种1000kV交流特高压输电线路分合闸系统。The invention relates to the field of ultra-high voltage transmission, in particular to a switching system for 1000kV AC ultra-high voltage transmission lines.
背景技术Background technique
由于我国可开发的水电资源近2/3在西部,煤炭资源的2/3在山西、陕西和内蒙古;但是我国2/3的用电负荷却分布在东部沿海和京广铁路沿线以东的经济发达地区。这样,就需要把能源基地发电的电量输送至电力需求大的中东部地区。Since nearly 2/3 of my country's exploitable hydropower resources are in the west, and 2/3 of coal resources are in Shanxi, Shaanxi and Inner Mongolia; however, 2/3 of my country's electricity load is distributed in the eastern coastal areas and economic areas east of the Beijing-Guangzhou Railway. developed areas. In this way, it is necessary to transmit the power generated by the energy base to the central and eastern regions where the power demand is large.
为了减少输电损耗,提高输电质量,我国目前开始研制特高压输电技术。特高压交流输电,是指1000kV及以上电压等级的交流输电工程及相关技术。特高压输电技术具有远距离、大容量、低损耗和经济性等特点。In order to reduce transmission loss and improve transmission quality, my country is currently developing UHV transmission technology. UHV AC transmission refers to AC transmission projects and related technologies with a voltage level of 1000kV and above. UHV transmission technology has the characteristics of long distance, large capacity, low loss and economy.
特高压电力系统中,当输电线路断路器进行合分闸操作时,将产生多种操作过电压。对于我国1000kV交流特高压输电系统来说,由于特高压线路自身的无功功率很大,每100km线路的无功功率可达530Mvar左右。再加上我国特高压输电线路大都具有远距离、大容量输送电能的特点,使得我国特高压输电线路分合闸操作过电压等危害系统安全的过电压问题更加突出。In the UHV power system, when the transmission line circuit breaker performs closing and opening operations, various operating overvoltages will be generated. For the 1000kV AC UHV transmission system in my country, since the reactive power of the UHV line itself is very large, the reactive power of each 100km line can reach about 530Mvar. In addition, most of my country's UHV transmission lines have the characteristics of long-distance and large-capacity transmission of electric energy, which makes my country's UHV transmission line opening and closing operation overvoltage and other overvoltages that endanger system safety more prominent.
合分闸操作过电压会对线路设备和系统安全带来很大的影响,同时考虑电气设备制造和部分地区高海拔方面的因素,给我国特高压交流系统的过电压限制提出了非常高的要求。世界上已经有其它国家建成1000kV交流特高压输变电工程,但目前我国尚属首次采用1000kV特高压交流输电技术,并且由于我国国情与其它国家不同,因而不能照搬其它国家现有的技术和经验,需要对1000kV交流特高压输变电工程中的关键技术进行自主创新。The overvoltage of the closing and opening operation will have a great impact on the safety of line equipment and systems. At the same time, considering the factors of electrical equipment manufacturing and high altitude in some areas, it has put forward very high requirements for the overvoltage limit of my country's UHV AC system. . Other countries in the world have built 1000kV AC UHV power transmission and transformation projects, but at present, my country is the first to adopt 1000kV UHV AC power transmission technology, and because my country's national conditions are different from other countries, it is impossible to copy the existing technology and experience of other countries , It is necessary to independently innovate the key technologies in the 1000kV AC UHV power transmission and transformation project.
因此,设计开发应用于1000kV交流特高压输电线路分合闸系统,通过合理代价将危害设备安全及系统运行可靠性的过电压问题限制在合理水平内,是特高压输电领域技术人员急需解决的技术问题。Therefore, the design and development of the opening and closing system for 1000kV AC UHV transmission lines to limit the overvoltage problem that endangers equipment safety and system operation reliability to a reasonable level at a reasonable cost is a technology that technicians in the UHV transmission field urgently need to solve. question.
发明内容Contents of the invention
本发明所要解决的技术问题是提供一种1000kV交流特高压输电线路分合闸系统,能够满足1000kV交流特高压输电系统的要求。The technical problem to be solved by the present invention is to provide a 1000kV AC UHV transmission line opening and closing system, which can meet the requirements of the 1000kV AC UHV transmission system.
为解决上述技术问题,本发明提供了一种1000kV交流特高压输电线路分合闸系统,所述系统包括:馈电侧系统UHV变压器、馈电侧UHV断路器、特高压输电线路、受电侧UHV断路器、以及受电侧系统UHV变压器;In order to solve the above technical problems, the present invention provides a 1000kV AC UHV transmission line opening and closing system, the system includes: feeder side system UHV transformer, feeder side UHV circuit breaker, UHV transmission line, power receiving side UHV circuit breakers, and UHV transformers for receiving side systems;
所述馈电侧UHV断路器一端与所述馈电侧系统UHV变压器的高压侧母线相联,另一端经所述特高压输电线路接受电侧UHV断路器的一端;所述受电侧UHV断路器的另一端接所述受电侧系统UHV变压器的高压侧母线;One end of the UHV circuit breaker on the feeder side is connected to the high-voltage side bus bar of the UHV transformer of the feeder-side system, and the other end receives one end of the UHV circuit breaker on the power-side through the UHV transmission line; the UHV circuit breaker on the power-receiving side The other end of the device is connected to the high-voltage side bus bar of the UHV transformer of the receiving side system;
其中,所述馈电侧UHV断路器用于实现所述特高压输电线路与所述馈电侧系统UHV变压器之间的分合闸操作;所述受电侧UHV断路器用于实现所述特高压输电线路与所述受电侧系统UHV变压器之间的分合闸操作;Wherein, the UHV circuit breaker on the feeding side is used to realize the opening and closing operation between the UHV power transmission line and the UHV transformer on the feeding side; the UHV circuit breaker on the receiving side is used to realize the UHV power transmission Opening and closing operations between the line and the UHV transformer of the receiving side system;
所述馈电侧系统UHV变压器和受电侧系统UHV变压器均为UHV升压变压器,用于实现500kV超高压交流电与1000kV特高压交流电以及110kV高压交流电之间的转化,其中压侧输入500kV超高压交流电,其高压侧输出1000kV特高压交流电,其低压侧输出110kV高压交流电Both the UHV transformer of the feeding side system and the UHV transformer of the receiving side system are UHV step-up transformers, which are used to realize the conversion between 500kV ultra-high voltage alternating current, 1000kV ultra-high voltage alternating current and 110kV high-voltage alternating current, wherein the voltage side inputs 500kV ultra-high voltage Alternating current, its high-voltage side outputs 1000kV UHV AC, and its low-voltage side outputs 110kV high-voltage AC
所述馈电侧UHV断路器和所述受电侧UHV断路器均装设合闸电阻,而不装设分闸电阻。Both the UHV circuit breaker on the feeding side and the UHV circuit breaker on the receiving side are equipped with a closing resistor, but not an opening resistor.
优选地,所述馈电侧UHV断路器包括:馈电侧主开关、馈电侧电阻开关、以及馈电侧合闸电阻;Preferably, the feeder-side UHV circuit breaker includes: a feeder-side main switch, a feeder-side resistance switch, and a feeder-side closing resistor;
所述馈电侧合闸电阻的一端与所述馈电侧主开关的一端共同接所述馈电侧系统UHV变压器的高压侧;所述馈电侧合闸电阻的另一端与所述馈电侧电阻开关的一端相联;所述馈电侧电阻开关的另一端与所述馈电侧主开关的另一端共同接所述特高压输电线路;One end of the feeding-side switching resistor and one end of the feeding-side main switch are connected to the high-voltage side of the feeding-side system UHV transformer; the other end of the feeding-side switching resistor is connected to the feeding One end of the side resistance switch is connected; the other end of the feed-side resistance switch and the other end of the feed-side main switch are jointly connected to the UHV transmission line;
其中,所述馈电侧合闸电阻与所述馈电侧电阻开关串联,用于限制特高压输电线路的合闸操作过电压。Wherein, the feeding-side closing resistor is connected in series with the feeding-side resistive switch, which is used to limit the overvoltage of the closing operation of the UHV transmission line.
优选地,所述馈电侧合闸电阻的取值为400~600欧,其接入时间为8~11ms。Preferably, the switching resistance of the feeder side has a value of 400-600 ohms, and its connection time is 8-11 ms.
优选地,所述受电侧UHV断路器包括:受电侧主开关、受电侧电阻开关、以及受电侧合闸电阻;Preferably, the UHV circuit breaker on the receiving side includes: a main switch on the receiving side, a resistance switch on the receiving side, and a closing resistor on the receiving side;
所述受电侧合闸电阻的一端与所述受电侧主开关的一端共同接所述受电侧系统UHV变压器的高压侧;所述受电侧合闸电阻的另一端与所述受电侧电阻开关的一端相联;所述受电侧电阻开关的另一端与所述受电侧主开关的另一端共同接所述特高压输电线路;One end of the receiving-side closing resistor and one end of the receiving-side main switch are connected to the high-voltage side of the receiving-side system UHV transformer; the other end of the receiving-side closing resistor is connected to the receiving-side main switch. One end of the resistance switch on the power receiving side is connected; the other end of the resistance switch on the receiving side and the other end of the main switch on the receiving side are jointly connected to the UHV transmission line;
其中,所述受电侧合闸电阻与所述受电侧电阻开关串联,用于限制特高压输电线路的合闸操作过电压。Wherein, the receiving-side closing resistor is connected in series with the receiving-side resistive switch, and is used to limit the overvoltage of the closing operation of the UHV transmission line.
优选地,所述受电侧合闸电阻的取值为400~600欧,其接入时间为8~11ms。Preferably, the closing resistance of the power receiving side has a value of 400-600 ohms, and its connection time is 8-11 ms.
与现有技术相比,本发明具有以下优点:Compared with the prior art, the present invention has the following advantages:
本发明所述1000kV交流特高压输电线路分合闸系统,包括馈电侧系统UHV变压器、馈电侧UHV断路器、特高压输电线路、受电侧UHV断路器、以及受电侧系统UHV变压器;所述馈电侧UHV断路器一端与所述馈电侧系统UHV变压器的高压侧母线相联,另一端经所述特高压输电线路接受电侧UHV断路器的一端;所述受电侧UHV断路器的另一端接所述受电侧系统UHV变压器的高压侧母线。The opening and closing system of the 1000kV AC UHV transmission line of the present invention includes a UHV transformer of the feeding side system, a UHV circuit breaker of the feeding side, an UHV transmission line, a UHV circuit breaker of the receiving side, and a UHV transformer of the receiving side system; One end of the UHV circuit breaker on the feeder side is connected to the high-voltage side bus bar of the UHV transformer of the feeder-side system, and the other end receives one end of the UHV circuit breaker on the power-side through the UHV transmission line; the UHV circuit breaker on the power-receiving side The other end of the transformer is connected to the high-voltage side busbar of the UHV transformer of the receiving side system.
基于对典型的特高压交流输电系统合闸、分闸操作过电压以及断路器暂态恢复电压的电磁暂态仿真研究结果,本发明所述分合闸系统,为确保将1000kV线路合闸、分闸操作过电压以及断路器暂态恢复限制在允许的范围内,除包括装设1000kV线路高抗以及额定电压为828kV的避雷器外,应对UHV断路器装设合闸电阻。本发明所述分合闸系统降低了工程造价,提高了设备的可靠性以及整个特高压系统的运行可靠性。Based on the electromagnetic transient simulation research results of the typical UHV AC transmission system closing and opening operation overvoltage and the transient recovery voltage of the circuit breaker, the opening and closing system of the present invention is designed to ensure that the 1000kV line is closed and opened. The gate operation overvoltage and the transient recovery of the circuit breaker are limited within the allowable range. In addition to the installation of a 1000kV line high-resistance and a surge arrester with a rated voltage of 828kV, a closing resistor should be installed on the UHV circuit breaker. The opening and closing system of the invention reduces the engineering cost, improves the reliability of the equipment and the operation reliability of the whole UHV system.
附图说明Description of drawings
图1为本发明所述1000kV交流特高压输电线路分合闸系统结构图;Fig. 1 is the structural diagram of the opening and closing system of the 1000kV AC UHV transmission line of the present invention;
图2为合闸空载情况下、特高压输电线路的等值电路图。Figure 2 is the equivalent circuit diagram of the UHV transmission line under the condition of closing and no load.
具体实施方式Detailed ways
本发明所要解决的技术问题是提供一种1000kV交流特高压输电线路分合闸系统,能够通过合理代价将危害设备安全及系统运行可靠性的过电压问题限制在合理水平内,满足1000kV交流特高压输电系统的要求。The technical problem to be solved by the present invention is to provide a 1000kV AC UHV transmission line opening and closing system, which can limit the overvoltage problem that endangers equipment safety and system operation reliability to a reasonable level at a reasonable cost, and meets the requirements of 1000kV AC UHV transmission system requirements.
为使本发明的上述目的、特征和优点能够更加明显易懂,下面结合附图和具体实施方式对本发明作进一步详细的说明。In order to make the above objects, features and advantages of the present invention more comprehensible, the present invention will be further described in detail below in conjunction with the accompanying drawings and specific embodiments.
参照图1,为本发明所述1000kV交流特高压输电线路分合闸系统结构图。Referring to FIG. 1 , it is a structural diagram of the opening and closing system of the 1000kV AC UHV transmission line according to the present invention.
所述分合闸系统包括:馈电侧系统UHV变压器10、馈电侧UHV断路器20、特高压输电线路30、受电侧UHV断路器40、受电侧系统UHV变压器50。The opening and closing system includes:
所述馈电侧系统UHV变压器10和受电侧系统UHV变压器50均为UHV(特高压,Ultra High Voltage)升压变压器,用于实现500kV超高压交流电与1000kV特高压交流电以及110kV高压交流电之间的转化,其中压侧输入500kV超高压交流电,其高压侧输出1000kV特高压交流电,其低压侧输出110kV高压交流电。The
所述馈电侧UHV断路器20一端与所述馈电侧系统UHV变压器10的高压侧母线相联,另一端经所述特高压输电线路30接受电侧UHV断路器40的一端;所述受电侧UHV断路器40的另一端接所述受电侧系统UHV变压器50的高压侧母线。One end of the feeder-side
其中,所述馈电侧UHV断路器20用于实现所述特高压输电线路30与所述馈电侧系统UHV变压器10之间的分合闸操作;所述受电侧UHV断路器40用于实现所述特高压输电线路30与所述受电侧系统UHV变压器50之间的分合闸操作。Wherein, the
所述特高压输电线路30用于输送1000kV特高压交流电,线路上可根据无功补偿需要相应装设高压电抗器等UHV设备。The
如图1所示,所述馈电侧UHV断路器20包括:馈电侧主开关K11、馈电侧电阻开关K12、以及馈电侧合闸电阻RH1。As shown in FIG. 1 , the feeder-side
所述馈电侧合闸电阻RH1的一端与所述馈电侧主开关K11的一端共同接所述馈电侧系统UHV变压器10的高压侧;所述馈电侧合闸电阻RH1的另一端与所述馈电侧电阻开关K12的一端相联;所述馈电侧电阻开关K12的另一端与所述馈电侧主开关K11的另一端共同接所述特高压输电线路30。One end of the feeding-side switching resistor R H1 and one end of the feeding-side main switch K11 are connected to the high-voltage side of the feeding-side
其中,所述馈电侧合闸电阻RH1与所述馈电侧电阻开关K12串联,用于限制特高压输电线路的合闸操作过电压。Wherein, the feeding-side switching resistor R H1 is connected in series with the feeding-side resistance switch K12 to limit the overvoltage of the switching-on operation of the UHV transmission line.
如图1所示,所述受电侧UHV断路器40包括:受电侧主开关K21、受电侧电阻开关K22、以及受电侧合闸电阻RH2。As shown in FIG. 1 , the receiving-side
所述受电侧合闸电阻RH2的一端与所述受电侧主开关K21的一端共同接所述受电侧系统UHV变压器50的高压侧;所述受电侧合闸电阻RH2的另一端与所述受电侧电阻开关K22的一端相联;所述受电侧电阻开关K22的另一端与所述受电侧主开关K21的另一端共同接所述特高压输电线路30。One end of the receiving-side closing resistor R H2 and one end of the receiving-side main switch K21 are connected to the high-voltage side of the receiving-side
其中,所述受电侧合闸电阻RH2与所述受电侧电阻开关K22串联,用于限制特高压输电线路的合闸操作过电压。Wherein, the closing resistor R H2 on the receiving side is connected in series with the resistive switch K22 on the receiving side, and is used to limit the overvoltage of the closing operation of the UHV transmission line.
操作过电压是在L-C回路工作状态发生变化引起的过渡过程中出现的。考虑到过电压问题对设备造价和系统安全的影响,目前国外推荐的特高压系统相对地统计操作过电压水平限制目标为1.6~1.8p.u。我国则因考虑到单段特高压线路输电距离较长、以及部分地区海拔的影响,推荐操作过电压限制目标为:对线路两端变电站、开关站设备应限制在1.6p.u;对于长线路的线路中间部分限制在1.7p.u以下。The operating overvoltage occurs during the transition process caused by the change of the working state of the L-C circuit. Considering the impact of overvoltage problems on equipment cost and system safety, the relative statistical operating overvoltage level limit target for UHV systems recommended abroad is 1.6~1.8p.u. In my country, considering the long transmission distance of a single UHV line and the influence of altitude in some areas, the recommended operating overvoltage limit target is: for substations and switchyard equipment at both ends of the line, it should be limited to 1.6p.u; for long lines The middle section is limited to under 1.7p.u.
相关研究结果表明,对于1000kV特高压输电线路,如果仅靠输电线路两侧的MOA(避雷器)限制合闸操作过电压,则当其线路长度超过200km时,线路中间部位相对地统计操作过电压超过1.8p.u;当线路长度增加到400~600km时,线路中间部位相对地统计操作过电压就增加到1.95~2.10p.u,相间统计过电压增加到3.5~3.5p.u。因此,对大部分特高压线路仅靠MOA限制合闸过电压是不够的,本发明提出的1000kV交流特高压输电线路分合闸系统中,为所述馈电侧UHV断路器20设置馈电侧合闸电阻RH1、以及为所述受电侧UHV断路器40设置受电侧合闸电阻RH2,用于对线路合闸操作时产生的过电压起抑制作用。Relevant research results show that for a 1000kV UHV transmission line, if only the MOA (lightning arrester) on both sides of the transmission line is used to limit the closing operation overvoltage, when the line length exceeds 200km, the statistical operation overvoltage in the middle part of the line will exceed 1.8pu; when the line length increases to 400-600km, the relative statistical operating overvoltage of the middle part of the line increases to 1.95-2.10pu, and the phase-to-phase statistical overvoltage increases to 3.5-3.5pu. Therefore, it is not enough to rely on MOA to limit the closing overvoltage for most UHV lines. In the opening and closing system of 1000kV AC UHV transmission lines proposed by the present invention, the
其具体操作过程可以通过图2所示合闸空载情况下、特高压输电线路的等值电路图进行说明。The specific operation process can be illustrated by the equivalent circuit diagram of the UHV transmission line in the case of closing and no load shown in Figure 2.
其中,如图2所示,在合闸空载情况下,可以认为所述特高压输电线路30一侧通过馈电侧UHV断路器20接所述馈电侧系统UHV变压器10,另一端与所述受电侧UHV断路器40断开、末端悬空。此时,为简化起见,将所述特高压输电线路用等值电阻R、等值电感L、以及等值电容C等效代替。Wherein, as shown in FIG. 2 , in the case of closing and no load, it can be considered that one side of the
所述特高压输电线路的合闸过程分为两个阶段:第一阶段为馈电侧电阻开关K12先合上、馈电侧合闸电阻RH1接入回路;第二阶段为馈电侧主开关K11合上,馈电侧合闸电阻RH1短接;整个合闸过程结束。The closing process of the UHV transmission line is divided into two stages: the first stage is that the feeder side resistance switch K12 is first closed, and the feeder side closing resistor R H1 is connected to the circuit; the second stage is that the feeder side main The switch K11 is closed, and the closing resistor R H1 of the feeding side is short-circuited; the whole closing process ends.
无论对馈电侧还是受电侧,合闸过程中,合闸电路对自由分量起到阻尼作用,降低了合闸操作过电压幅值。从限制合闸操作过电压的角度出发,合上电阻开关K2时希望合闸电阻大些;而合上主开关K1时希望合闸电阻小些。因此,需要结合实际工程情况对合闸电阻RH的阻值进行合理选择。本发明实施例所述合闸电阻RH的取值可以为400~600欧,其接入时间可以为8~11ms。Regardless of the feeder side or the power receiving side, during the closing process, the closing circuit plays a damping role on the free component, reducing the overvoltage amplitude of the closing operation. From the point of view of limiting the overvoltage of closing operation, it is hoped that the closing resistance is larger when the resistance switch K2 is closed; and that the closing resistance is smaller when the main switch K1 is closed. Therefore, it is necessary to make a reasonable selection of the resistance value of the closing resistor R H in combination with the actual engineering situation. The value of the closing resistor R H in the embodiment of the present invention may be 400-600 ohms, and the switching time may be 8-11 ms.
即,在实际应用中,所述馈电侧合闸电阻RH1、以及受电侧合闸电阻RH2的取值均需要根据实际工程情况据具体设定。而本发明实施例中,所述馈电侧合闸电阻RH1的取值可以为400~600欧,其接入时间可以为8~11ms;所述受电侧合闸电阻RH2的取值也可以为400~600欧,其接入时间可以为8~11ms。That is, in practical applications, the values of the switching resistor R H1 on the feeder side and the switching resistor R H2 on the receiving side need to be specifically set according to actual engineering conditions. However, in the embodiment of the present invention, the value of the switching resistor R H1 on the feeder side can be 400-600 ohms, and the connection time can be 8-11 ms; the value of the switching resistor R H2 on the receiving side can be It can also be 400-600 ohms, and the access time can be 8-11 ms.
传统观点认为,对于特高压输电线路分合闸系统的断路器需要加设分闸电阻,用于抑制分闸过电压。但是本发明技术人员通过研究发现:对特高压交流线路合分闸系统,仅需装设合闸电阻,而不必装设分闸电阻即可满足相应过电压要求,同时又能避免装设分闸电阻带来的一些问题。The traditional point of view is that for the circuit breaker of the UHV transmission line opening and closing system, it is necessary to add an opening resistor to suppress the opening overvoltage. However, the technicians of the present invention have found through research that: for the UHV AC line closing and opening system, only the closing resistor needs to be installed, and the corresponding overvoltage requirements can be met without installing the opening resistor, and at the same time, the installation of the opening resistor can be avoided. Some problems caused by resistance.
其具体研究包括以下几个方面:Its specific research includes the following aspects:
(1)基于对交流特高压试验示范工程分闸操作过电压的电磁暂态仿真研究结果,对1000kV断路器仅装设合闸电阻而不装设分闸电阻条件下分析采用其它措施对分闸过电压的限制效果,证明采用其它限制措施替代装设断路器分闸电阻是可行有效的。(1) Based on the electromagnetic transient simulation research results of the overvoltage of the opening operation of the AC UHV test demonstration project, the 1000kV circuit breaker is only equipped with a closing resistor but not an opening resistor. The limiting effect of the overvoltage proves that it is feasible and effective to use other limiting measures instead of installing the opening resistor of the circuit breaker.
针对特高压交流输电线路的分闸操作过电压进行电磁暂态仿真试验。试验结果表明,大多数情况下,仅靠额定电压为828kV的MOA和常规线路高抗就可以将变电站、开关站的甩负荷分闸操作过电压限制在1.6p.u以下;将线路杆塔部分的过电压限制在1.7p.u以下;另外使用良导体地线多点接地的方式也可以限制单相接地故障甩负荷操作过电压;而对于一级升压送电系统,则可通过对发电厂装机容量及送出线路长度提出限制来满足过电压水平的要求。对于故障清除转移操作过电压,仅靠线路两端的额定电压为828kV的MOA可以将特高压输电线路清除单相接地故障转移操作过电压限制在允许范围内;清除多相故障时产生的转移操作过电压,由于它不会危及变电设备的安全(在线路两端仍在1.6p.u以下),仅影响到线路杆塔部分绝缘,而该绝缘为自恢复绝缘,加之其出现概率极低,没有必要采取更多的措施。如一定要考虑,可采取在线路中部加装一组MOA的方法即可将过电压限制在允许范围内,该措施与装设分闸电阻相比,既经济又比较可靠。The electromagnetic transient simulation test is carried out for the overvoltage of the opening operation of the UHV AC transmission line. The test results show that in most cases, only the MOA with a rated voltage of 828kV and the high reactance of conventional lines can limit the overvoltage of substations and switching stations to less than 1.6p.u; It is limited below 1.7p.u; in addition, the multi-point grounding method of good conductor ground wire can also limit the overvoltage of single-phase ground fault load shedding operation; Line lengths are limited to meet overvoltage level requirements. For the overvoltage of the fault clearing transfer operation, only the MOA with a rated voltage of 828kV at both ends of the line can limit the overvoltage of the UHV transmission line to clear the single-phase ground fault transfer operation within the allowable range; Voltage, because it will not endanger the safety of substation equipment (it is still below 1.6p.u at both ends of the line), it only affects the insulation of the line tower, and the insulation is self-restoring insulation, and its occurrence probability is extremely low, so there is no need to take measures More measures. If it must be considered, the method of installing a group of MOA in the middle of the line can limit the overvoltage within the allowable range. Compared with installing the opening resistor, this measure is more economical and more reliable.
(2)结合国内外电网运行经验,对过电压较严重工况的出现概率情况、以及分合闸电阻本身出现故障的概率情况进行分析,提出装设分闸电阻的经济性存在问题。(2) Combined with domestic and foreign power grid operation experience, the probability of occurrence of severe overvoltage conditions and the probability of failure of the opening and closing resistors are analyzed, and the economical problems of installing opening and closing resistors are pointed out.
根据我国500kV电网运行情况的统计情况,截至2002年只统计到一次三相短路故障。而对于特高压输电线路,发生两相与三相短路故障的可能性估计会更低。对于特高压输电线路分闸系统的断路器,若装设分闸电阻,由于分闸电阻本身出现故障的概率远大于两相或三相短路等严重短路故障;若采用一个电阻同时抑制合闸过电压和分闸过电压,则其损坏率还要更高;由此说明,用一种损坏率相对较高的元件去保护一种出现概率低得多的故障,是不经济的、不合理的。According to the statistical situation of the operation of 500kV power grid in my country, as of 2002, only one three-phase short-circuit fault was counted. For UHV transmission lines, the possibility of two-phase and three-phase short-circuit faults is estimated to be lower. For the circuit breaker of the UHV transmission line opening system, if the opening resistor is installed, the probability of failure of the opening resistor itself is much higher than that of serious short-circuit faults such as two-phase or three-phase short circuit; overvoltage and opening overvoltage, the damage rate is even higher; thus, it is uneconomical and unreasonable to use a component with a relatively high damage rate to protect a fault with a much lower probability of occurrence .
(3)对特高压交流试验示范工程断路器,在装设分闸电阻和不装设分闸电阻两种情况下,分别对其进行开断失步故障以及各种短路故障时的TRV仿真。根据仿真研究的结果,提出可以不必装设分闸电阻。(3) For the circuit breaker of the UHV AC test demonstration project, the TRV simulations of the out-of-step fault and various short-circuit faults were carried out under the two conditions of installing the opening resistor and not installing the opening resistor. According to the results of the simulation study, it is proposed that the opening resistor may not be installed.
根据我国及IEC高压交流断路器标准中规定的断路器考核条件要求,考虑特高压试验示范工程本期及远期系统条件,对断路器开断严重失步解列故障以及端部三相短路等严重短路故障时的TRV情况进行仿真研究。本发明相关研究结果表明,在不使用分闸电阻条件下,晋东南、南阳及荆门三个特高压站内断路器TRV的最大峰值和上升率均可满足表1中所列的我国1100kV断路器电力行业标准和IEC断路器标准扩展中规定的TRV试验参数要求。According to the requirements of circuit breaker assessment conditions stipulated in my country and IEC high-voltage AC circuit breaker standards, considering the current and long-term system conditions of the UHV test demonstration project, serious out-of-step disconnection failures and three-phase short circuits at the end of the circuit breaker should be considered. The TRV situation in severe short-circuit faults is simulated and studied. The relevant research results of the present invention show that the maximum peak value and rising rate of the circuit breaker TRV in the three UHV stations in Jindongnan, Nanyang and Jingmen can meet the 1100kV circuit breaker power in my country listed in Table 1 without using the opening resistor. TRV test parameter requirements specified in industry standards and IEC circuit breaker standard extensions.
而特高压断路器装设600欧分闸电阻后,仅对小短路电流情况下断路器主断口TRV峰值和上升率有一定降低作用,而对额定短路开断电流(50kA)条件下的主断口TRV的限制效果不明显;而开断失步故障时,尽管对主断口TRV水平有一定降低,但辅助断口的TRV峰值则较无分闸电阻情况下有明显增大,甚至超过了相关标准中规定的试验参数要求,而目前很多厂家的设备制造能力及试验考核条件无法达到上述要求,同时也提高了设备造价。After the UHV circuit breaker is installed with a 600 ohm opening resistor, it only has a certain effect on reducing the peak value and rising rate of the main fracture TRV of the circuit breaker under the condition of small short-circuit current, while the main fracture under the condition of rated short-circuit breaking current (50kA) The limiting effect of TRV is not obvious; when the out-of-synchronization fault occurs, although the TRV level of the main fracture has a certain decrease, the TRV peak value of the auxiliary fracture is significantly increased compared with the case of no opening resistance, and even exceeds the relevant standards. The specified test parameter requirements, but the current equipment manufacturing capabilities and test assessment conditions of many manufacturers cannot meet the above requirements, and also increase the equipment cost.
因此从限制特高压断路器TRV的角度而言,可以不必装设分闸电阻。Therefore, from the perspective of limiting the TRV of the UHV circuit breaker, it is not necessary to install a tripping resistor.
表1 1100kV断路器恢复电压试验参数要求Table 1 1100kV circuit breaker recovery voltage test parameter requirements
(4)基于对交流特高压试验示范工程断路器开断短路电流时零点漂移问题机理和影响因素的研究分析结果,提出特高压短路电流零点漂移出现概率极低,并纠正了装设分闸电阻可以消除零点漂移的错误判断。(4) Based on the research and analysis results of the zero drift problem mechanism and influencing factors when the circuit breaker of the AC UHV test demonstration project breaks the short-circuit current, it is proposed that the occurrence probability of the zero drift of the UHV short-circuit current is extremely low, and the installation of the opening resistor is corrected. Misjudgment of zero drift can be eliminated.
传统理论认为,对断路器装设分闸电阻可以消除断路器开断短路电流时的零点漂移问题。但是通过本发明对零点漂移问题的相关研究结果认为,零点漂移现象的产生主要与两个因素有关:一是故障时刻;二是短路电流交流分量与负荷电流的比值及负荷电流性质,并认为零点漂移主要出现在小短路电流系统中。可见断路器装设分闸电阻与零点漂移无关,无法消除断路器开断短路电流时的零点漂移问题。According to the traditional theory, installing an opening resistor on the circuit breaker can eliminate the problem of zero point drift when the circuit breaker breaks the short-circuit current. However, according to the relevant research results of the present invention on the zero point drift problem, the generation of the zero point drift phenomenon is mainly related to two factors: one is the moment of failure; the other is the ratio of the AC component of the short circuit current to the load current and the nature of the load current. Drift mainly occurs in small short-circuit current systems. It can be seen that the installation of the opening resistor of the circuit breaker has nothing to do with the zero point drift, and the problem of zero point drift when the circuit breaker breaks the short-circuit current cannot be eliminated.
(5)对1000kV断路器装设分闸电阻时的热容量问题进行研究,分析采用分合闸电阻时的热容量要求,提出在实际工程中1000kV断路器采用分闸电阻的可行性不大。(5) Research on the thermal capacity of 1000kV circuit breaker when the opening resistor is installed, analyze the thermal capacity requirements when using the opening and closing resistor, and propose that it is not feasible to use the opening resistor for 1000kV circuit breaker in actual engineering.
由于分合闸一般共用一个电阻,因此能量问题是使用分闸电阻的最大问题。对分合闸电阻能量其决定作用的并不是限制操作过电压过程的能量消耗,而是线路断路器其它分合要求,这个要求也反映在断路器试验要求中。根据断路器相关标准、规范、技术条件规定的试验条件计算了特高压断路器合/分闸电阻热容量,并对晋东南-南阳-荆门特高压输电系统在本期及远期系统条件下可能出现的故障及操作下合/分闸电阻吸收的能耗进行仿真研究。综合这两方面计算结果,对断路器合/分闸电阻能耗提出以下建议:(1)要求断路器能够承受BTF分闸+单次失步合分操作,断路器带400~600Ω合/分闸电阻(合分闸共用电阻)时,合/分闸电阻吸收能耗能力分别要求不低于165~247MJ,如表2所示;(2)如允许断路器在失步条件下两次合分(CO-t-CO),则对于带600Ω合/分闸电阻的断路器(合分闸共用电阻),合/分闸电阻能耗为247.3MJ(不考虑电阻在两次操作时间间隔内的散热情况)。目前很少有断路器生产厂家可以达到上述制造能力,其造价也相当昂贵,同时还增加了设备损坏的概率,因此应用于实际工程的可行性不大。Since the opening and closing generally share a resistor, the energy problem is the biggest problem when using the opening resistor. The decisive role of the opening and closing resistance energy is not to limit the energy consumption in the process of operating overvoltage, but other opening and closing requirements of the circuit breaker. This requirement is also reflected in the circuit breaker test requirements. According to the test conditions stipulated in the relevant standards, specifications and technical conditions of the circuit breaker, the heat capacity of the closing/opening resistance of the UHV circuit breaker is calculated, and the possible occurrence of the Jindongnan-Nanyang-Jingmen UHV transmission system under the current and long-term system conditions The energy consumption absorbed by the closing/opening resistor under the fault and operation is simulated and studied. Based on the calculation results of these two aspects, the following suggestions are put forward for the energy consumption of the closing/opening resistance of the circuit breaker: (1) The circuit breaker is required to be able to withstand BTF opening + single out-of-step closing and opening operation, and the circuit breaker is equipped with 400~600Ω When using the gate resistance (common resistance for closing and opening), the absorbing energy consumption capacity of the closing and opening resistors should not be less than 165~247MJ, as shown in Table 2; (2) If the circuit breaker is allowed to close twice under the condition of out of step Open (CO-t-CO), then for a circuit breaker with a 600Ω closing/opening resistance (common resistance for closing and opening), the energy consumption of the closing/opening resistance is 247.3MJ (regardless of the resistance in the two operation time intervals heat dissipation). At present, there are very few circuit breaker manufacturers that can achieve the above-mentioned manufacturing capacity, and its cost is also quite expensive. At the same time, it also increases the probability of equipment damage, so it is not feasible to apply it to actual projects.
表2 断路器合/分闸电阻热容量建议值Table 2 Suggested value of thermal capacity of closing/opening resistor of circuit breaker
(6)根据本发明相关研究结果,断路器装设分/合闸电阻时,限制操作过电压所要求的阻值很难一致,研究表明分合闸电阻取值大时会降低限制操作过电压的效果,如分合闸电阻为700Ω,经计算无法满足特高压试验示范工程的过电压限制要求;而分合闸电阻阻值降低时,其所需的能耗要求又将大大增加。基于上述考虑,提出不采用分闸电阻,可根据情况采用400~600Ω合闸电阻,其能耗要求取45~30MJ。(6) According to the relevant research results of the present invention, when the circuit breaker is equipped with opening/closing resistance, the resistance value required to limit the operating overvoltage is difficult to be consistent. Research shows that when the opening and closing resistance is large, the limit operation overvoltage will be reduced. If the opening and closing resistance is 700Ω, it cannot meet the overvoltage limit requirements of the UHV test demonstration project; and when the resistance of the opening and closing resistance is reduced, the required energy consumption requirements will increase greatly. Based on the above considerations, it is proposed not to use the opening resistor, and the closing resistor of 400-600Ω can be used according to the situation, and the energy consumption requirement is 45-30MJ.
综合上述各方面的研究成果,本发明提出一种特高压交流线路合分闸系统,即1000kV线路断路器需装设合闸电阻,而不必装设分闸电阻。合闸电阻的阻值一般取400~600欧并可根据不同工程具体选择阻值,接入时间取8~11ms,能耗要求取45~30MJ。Based on the above-mentioned research results, the present invention proposes a UHV AC line closing and opening system, that is, a 1000kV line circuit breaker needs to be equipped with a closing resistor instead of an opening resistor. The resistance value of the closing resistor is generally 400-600 ohms and can be selected according to different projects. The connection time is 8-11ms, and the energy consumption requirement is 45-30MJ.
本发明所述1000kV交流特高压输电线路分合闸系统,包括:UHV变压器、UHV断路器、特高压输电线路、以及UHV设备侧;所述UHV断路器一端与所述UHV变压器的高压侧相联,另一端经所述特高压输电线路接受电侧UHV系统,用于实现所述特高压输电线路与所述UHV变压器之间的分合闸操作;且所述UHV断路器装设合闸电阻但不装设分闸电阻。The 1000kV AC UHV transmission line opening and closing system of the present invention includes: UHV transformer, UHV circuit breaker, UHV transmission line, and UHV equipment side; one end of the UHV circuit breaker is connected to the high voltage side of the UHV transformer , and the other end receives the power-side UHV system through the UHV transmission line, and is used to realize the opening and closing operation between the UHV transmission line and the UHV transformer; and the UHV circuit breaker is equipped with a closing resistor but No opening resistor is installed.
基于对典型的特高压交流输电系统合闸操作过电压的电磁暂态仿真研究结果,本发明所述分合闸系统,为确保将1000kV线路合闸操作过电压限制在允许的范围内,除包括装设线路高抗以及额定电压为828kV的避雷针外,对UHV断路器装设合闸电阻。所述合闸电阻的阻值一般在400~600欧,并可根据不用工程具体选择阻值,其接入时间为8~11ms,能耗要求取45~30MJ。本发明所述分合闸系统降低了工程造价,提高了设备的可靠性以及整个特高压系统的运行可靠性。Based on the electromagnetic transient simulation research results of the typical UHV AC transmission system closing operation overvoltage, the opening and closing system of the present invention, in order to ensure that the 1000kV line closing operation overvoltage is limited within the allowable range, in addition to including In addition to installing lightning rods with high impedance of the line and a rated voltage of 828kV, a closing resistor is installed on the UHV circuit breaker. The resistance value of the closing resistor is generally 400-600 ohms, and the resistance value can be selected according to different projects. The connection time is 8-11 ms, and the energy consumption requirement is 45-30 MJ. The opening and closing system of the invention reduces the engineering cost, improves the reliability of the equipment and the operation reliability of the whole UHV system.
进一步的,本发明也纠正了传统观念认为的:装设分闸电阻能够解决特高压系统可能出现的零点漂移现象、以及可以有效降低开断严重故障时的暂态恢复电压水平的效果等片面或错误论断。同时,采用断路器装设分闸电阻这种损坏率相对较高的元件去保护出现概率低得多且对变电站、开关站电气设备不造成太大损坏的多相故障分闸操作过电压,是不经济、不合理的。且装设分闸电阻在热容量问题以及能耗方便均存在一定的缺陷。Further, the present invention also corrects the one-sided or one-sided view that the installation of the opening resistor can solve the zero drift phenomenon that may occur in the UHV system, and can effectively reduce the transient recovery voltage level when breaking serious faults. Wrong assertion. At the same time, using the circuit breaker to install the opening resistor, which has a relatively high damage rate, to protect the multi-phase fault opening operation overvoltage that has a much lower probability of occurrence and does not cause too much damage to the electrical equipment of the substation and switch station. Uneconomical and unreasonable. And the installation of the opening resistor has certain defects in the heat capacity problem and the convenience of energy consumption.
因此,本发明所述分合闸系统的断路器仅装设合闸电阻、不装设分闸电阻,能够通过合理代价将危害设备安全及系统运行可靠性的过电压问题限制在合理水平内,满足1000kV交流特高压输电线路的要求。Therefore, the circuit breaker of the opening and closing system of the present invention is only equipped with a closing resistor and not an opening resistor, which can limit the overvoltage problem that endangers the safety of equipment and the reliability of system operation to a reasonable level at a reasonable cost. Meet the requirements of 1000kV AC UHV transmission lines.
以上对本发明所提供的一种1000kV交流特高压输电线路分合闸系统,进行了详细介绍,本文中应用了具体个例对本发明的原理及实施方式进行了阐述,以上实施例的说明只是用于帮助理解本发明的方法及其核心思想;同时,对于本领域的一般技术人员,依据本发明的思想,在具体实施方式及应用范围上均会有改变之处,综上所述,本说明书内容不应理解为对本发明的限制。Above, a kind of 1000kV AC UHV transmission line opening and closing system provided by the present invention has been introduced in detail. In this paper, specific examples have been used to illustrate the principle and implementation of the present invention. The description of the above embodiments is only for To help understand the method of the present invention and its core idea; at the same time, for those of ordinary skill in the art, according to the idea of the present invention, there will be changes in the specific implementation and scope of application. In summary, the content of this specification It should not be construed as a limitation of the invention.
Claims (5)
Priority Applications (2)
Application Number | Priority Date | Filing Date | Title |
---|---|---|---|
CN2009101682558A CN101640424B (en) | 2009-08-20 | 2009-08-20 | On-off system of 1000kV AC ultrahigh-voltage transmission line |
PCT/CN2010/001258 WO2011020303A1 (en) | 2009-08-20 | 2010-08-19 | Switch off breaker, switch on-off breaker, switch on-off system, and switch off method for ultra-high voltage alternating current transmission line |
Applications Claiming Priority (1)
Application Number | Priority Date | Filing Date | Title |
---|---|---|---|
CN2009101682558A CN101640424B (en) | 2009-08-20 | 2009-08-20 | On-off system of 1000kV AC ultrahigh-voltage transmission line |
Publications (2)
Publication Number | Publication Date |
---|---|
CN101640424A CN101640424A (en) | 2010-02-03 |
CN101640424B true CN101640424B (en) | 2011-09-28 |
Family
ID=41615274
Family Applications (1)
Application Number | Title | Priority Date | Filing Date |
---|---|---|---|
CN2009101682558A Active CN101640424B (en) | 2009-08-20 | 2009-08-20 | On-off system of 1000kV AC ultrahigh-voltage transmission line |
Country Status (2)
Country | Link |
---|---|
CN (1) | CN101640424B (en) |
WO (1) | WO2011020303A1 (en) |
Cited By (2)
Publication number | Priority date | Publication date | Assignee | Title |
---|---|---|---|---|
TWI501496B (en) * | 2013-06-06 | 2015-09-21 | Chang Chun Petrochemical Co | Uninterruptible power protection apparatus and manufacturing system for producing electrolytic copper foil |
CN111261448B (en) * | 2020-01-07 | 2022-07-05 | 平高集团有限公司 | Circuit breaker |
Families Citing this family (5)
Publication number | Priority date | Publication date | Assignee | Title |
---|---|---|---|---|
CN101640424B (en) * | 2009-08-20 | 2011-09-28 | 中国电力科学研究院 | On-off system of 1000kV AC ultrahigh-voltage transmission line |
CN102074948A (en) * | 2011-01-20 | 2011-05-25 | 清华大学 | System for limiting overvoltage in ultrahigh-voltage alternating current power transmission system |
CN103441518B (en) * | 2013-08-06 | 2016-04-20 | 国家电网公司 | Three-phase Power Flow distribution determination method in single-phase load and alternate load mixing situation |
CN105388415B (en) * | 2015-11-10 | 2019-12-27 | 中国电力科学研究院 | Circuit breaker on-off TRV capability evaluation method based on two-segment time scale |
CN112366673A (en) * | 2020-12-03 | 2021-02-12 | 青岛地铁科技有限公司 | Operation overvoltage suppression circuit and method for steel rail potential limiting device |
Family Cites Families (3)
Publication number | Priority date | Publication date | Assignee | Title |
---|---|---|---|---|
US4016485A (en) * | 1976-03-02 | 1977-04-05 | German Ivanovich Samorodov | Arrangement for limiting dynamic overvoltages |
CN100442411C (en) * | 2006-04-26 | 2008-12-10 | 王光顺 | Multi-stage arc suppressing breaking device for extra-high voltage circuit breaker |
CN101640424B (en) * | 2009-08-20 | 2011-09-28 | 中国电力科学研究院 | On-off system of 1000kV AC ultrahigh-voltage transmission line |
-
2009
- 2009-08-20 CN CN2009101682558A patent/CN101640424B/en active Active
-
2010
- 2010-08-19 WO PCT/CN2010/001258 patent/WO2011020303A1/en active Application Filing
Cited By (2)
Publication number | Priority date | Publication date | Assignee | Title |
---|---|---|---|---|
TWI501496B (en) * | 2013-06-06 | 2015-09-21 | Chang Chun Petrochemical Co | Uninterruptible power protection apparatus and manufacturing system for producing electrolytic copper foil |
CN111261448B (en) * | 2020-01-07 | 2022-07-05 | 平高集团有限公司 | Circuit breaker |
Also Published As
Publication number | Publication date |
---|---|
CN101640424A (en) | 2010-02-03 |
WO2011020303A1 (en) | 2011-02-24 |
Similar Documents
Publication | Publication Date | Title |
---|---|---|
CN101640424B (en) | On-off system of 1000kV AC ultrahigh-voltage transmission line | |
CN103208788B (en) | Intelligent Dynamic power network neutral point earthing method and the complete sets of equipment | |
CN203895766U (en) | Double busbar and double subsection based substation main wiring system | |
CN104767195A (en) | Small reactance value choose method during ultrahigh voltage autotransformer neutral point grounding in small reactance mode | |
CN201332275Y (en) | Variable voltage reactor of 500kV and uhv transmission lines | |
CN103259259B (en) | A kind of high resistance configuration-system and method suppressing 750kV many FACTS circuit electromagnetic transient problems | |
CN103887777A (en) | Automatic feeder protecting method for overhead line four-section three-contact structure | |
CN110277771A (en) | A Method of Improving the Interrupting Capability of Substation Short-circuit Current by T-connection of Lines | |
CN105356442B (en) | A kind of volume-regulating type arc-extinction system that dynamic passive compensation is adjusted | |
Hu et al. | Analysis on the necessity of high-voltage shunt reactors in power grid | |
CN209184242U (en) | A dispatchable controllable distribution network neutral point grounding device | |
CN111769518A (en) | A method for neutral point protection of power station transformers based on gap protection and arrester | |
CN207459723U (en) | Spare phase transformer quickly puts into arrangement | |
CN213279163U (en) | Arc suppression coil capacity increasing system of power distribution network | |
CN107342581A (en) | A kind of 500kV auto-transformers neutral point reactance selection method | |
CN203813447U (en) | Substation High Voltage Reactive Power Automatic Compensation Device | |
CN204304424U (en) | A kind of single-phase earthing superpotential transfer restraint device | |
CN203798982U (en) | Switch electric life test loop for extra-high voltage substation reactive compensation | |
CN112688333A (en) | Design method for primary system of extra-high voltage transformer substation | |
CN203387190U (en) | High-voltage reactive compensator | |
CN110112721A (en) | A kind of DC distribution net internal system overvoltage protection System and method for | |
Cao et al. | A new type of fault current limiter | |
CN201699326U (en) | Substation main wiring system based on intermediate-frequency quenching transformer | |
CN105470940B (en) | A kind of arc-extinguishing system that dynamic passive compensation is adjusted | |
CN203289089U (en) | Novel high-efficient arc-extinguishing lightning arrester separator |
Legal Events
Date | Code | Title | Description |
---|---|---|---|
C06 | Publication | ||
PB01 | Publication | ||
C10 | Entry into substantive examination | ||
SE01 | Entry into force of request for substantive examination | ||
C14 | Grant of patent or utility model | ||
GR01 | Patent grant |