Background technology
In some regional on-the-spot actual moving process, after outside the system busbar district single-phase fault taking place, the mutation current of passing through property appears in non-fault phase secondary circuit in the recent period, and misoperation has appearred in non-fault phase current differential protection.Its principal character is: distinguish outer single-phase fault, the peaked wave electric current of several cycles appears in non-fault mutually.The saturated criterion of the anti-CT of domestic protection equipment for busbar mainly is to utilize secondary current correctly on the progress of disease basis; be that CT can not enter saturated at once after the fault; one section linear work district is arranged; referring to Cheng Lijun etc. " based on the research of the CT saturation detection scheme of sampled value ". relay, 2000.28 (8): 19-21.Because non-fault phase fault starting and current differential protection move simultaneously, asynchronous method (time difference method) is judged to troubles inside the sample space, does not have Blocking Differential Protection, and non-fault is sent out trip signal mutually, has enlarged the accident scope.
These two kinds of phenomenons all are the behaviors of non-fault phase differential protection generation malfunction in the differential current protection.Get rid of line mutual-inductance in the testing crew investigation process at the scene item by item; increasing-aid current; the influence of factors such as protective device and secondary circuit defective; analyze the wiring of protection and secondary circuit; check the action behavior of protective device; set about from resolving the on-the-spot failure wave-recording information of extracting; according to on-the-spot operating current and voltage waveform; when bus or circuit generation single-phase fault; fault phase short circuit current is not very big; about the 5-6 during for rated current times; but DC component aperiodic with very big decay; the Current Transformer Secondary side of fault phase does not take place saturated; but be the meet burr mutation current of peaked wave that 2-3 cycle occur of non-fault, the direction of mutation current and the fault direction of short circuit current mutually are anti-phase substantially, and non-fault phase current produces distortion; non-fault phase differential current satisfies the ratio brake criterion; referring to Yuan Yubo, 5 snowy peaks, Deng Jieqing etc. " the current transformer three-phase current is gone here and there mutually to the influence of differential protection ". Automation of Electric Systems; 2010,34 (21): 65-68.The visible processing scheme to the problems referred to above of document is generally the saturation characteristic of current transformer is carried out verification at present; Whether the wiring of paying close attention to the secondary circuit neutral point has the phenomenon of loose contact or insulation damages; Carry out type selecting in strict accordance with the protective current transformer, technical conditions; processing method at secondary circuit such as to change to ineligible current transformer; referring to Yuan Yubo; 5 snowy peaks; Deng Jie is clear etc. and " the current transformer three-phase current is gone here and there mutually to the influence of differential protection ". Automation of Electric Systems; 2010,34 (21): 65-68.
Summary of the invention
Goal of the invention
The objective of the invention is: the fault phase current flows through the CT secondary side neutral line and is coupled with non-fault and causes non-fault mutually saturated during the resolution system fault, and time difference method is judged non-fault by accident the problem that causes non-fault phase differential protection action for troubles inside the sample space mutually.
Technical scheme
In order to solve above technical problem; the present invention proposes based on three-phase current amplitude proportion and difference stream harmonic wave; discern the saturated method of non-fault phase CT; it is characterized in that: utilize fault phase stalling current to brake non-fault phase; the non-fault phase of locking differential protection when non-fault is mutually saturated; simultaneously according to difference stream harmonic characteristic at a difference stream harmonic wave hour open differential protection, differential protection can be opened outlet when guaranteeing in double earthfault, the district high resistive fault.
The operating characteristics of the sudden change amount ratio-differential relay of general current differential protection is:
Wherein
Be sudden change amount difference stream amplitude,
Be prominent residual quantity stalling current amplitude,
Be differential startup threshold, k is the ratio restraint coefficient.
From the above mentioned, when non-fault occurs when saturated mutually, general non-fault sudden change amount mutually difference stream is bigger, and with non-fault sudden change amount mutually stalling current sizableness, so formula (1) and formula (2) are not enough to brake.But fault this moment sudden change amount mutually stalling current is generally bigger; based on these characteristics; the present invention adopts fault sudden change amount mutually stalling current to brake non-fault phase; when sudden change amount difference stream during greater than a certain proportion of maximal phase sudden change amount stalling current; open differential protection; otherwise Blocking Differential Protection, as the formula (3):
Wherein
Be maximal phase sudden change amount stalling current amplitude,
Be non-fault phase saturation mutation amount restraint coefficient.
It is different to consider that fault phase current when non-fault is mutually saturated flows through the pro rate relation of non-fault phase CT secondary circuit; and fault sudden change amount mutually stalling current can be decayed in time; the reliably locking in some cases of sudden change amount braking criterion; therefore the present invention adopts fault phase stable state stalling current to brake non-fault phase; when stable state difference stream during greater than a certain proportion of maximal phase stalling current; open differential protection, otherwise Blocking Differential Protection
Wherein
Be maximal phase stalling current amplitude,
For non-fault differs the stream amplitude,
Be the mutually saturated steady-state quantity restraint coefficient of non-fault.
In the taking into account system generating region during double earthfault; fault phase current difference is bigger; said method may cause the mistake locking; in order to reduce this risk; increase the open differentiation of difference stream harmonic wave; main is just in time opposite according to the time dependent trend of difference stream harmonic content that is troubles inside the sample space and the mutually saturated formation of non-fault; troubles inside the sample space difference stream harmonic content can change gradually in time and diminish; but not the harmonic content of the difference stream of the mutually saturated formation of fault can increase with changing gradually fault time; therefore the present invention adopts and judges that the method that harmonic component in the difference stream accounts for difference stream fundametal compoment ratio addresses the above problem; the harmonic component of being on duty in the stream hour; open differential protection, as the formula (5)
Wherein
Be the humorous wave amplitude of difference stream,
Be difference stream fundamental voltage amplitude.
The logic diagram of above method as shown in drawings.
Beneficial effect
1) brake non-fault phase mutually with fault, made full use of the mutually saturated substantive characteristics of non-fault, principle is simple and reliable, can reliable locking when the mutually saturated time difference method of non-fault is judged by accident.
2) this method does not only influence the responsiveness and the operating characteristics of the prominent difference of normal fault relay, can also well prevent misoperation differential when non-fault is mutually saturated, can not miss locking in situations such as evolved fault, developing faults.
3) utilize difference stream harmonic wave open, differential protection operating characteristics when not influencing evolved fault, when outside the bus district takes place, changeing in troubles inside the sample space, the district high resistive fault, can Blocking Differential Protection.
Embodiment
Embodiment below in conjunction with a half breaker bus mode of connection describes in further detail the present invention.But the invention is not restricted to given example.
1) AC sampling: the current sampling data that obtains each branch road of bus.
2) calculate each branch current sudden change amount
,
Sign branch road number.
3) calculate each branch current fundametal compoment
,
Sign branch road number.
4) calculate bus three-phase sudden change amount difference stream
, sudden change amount stalling current
, stable state difference stream
, the stable state stalling current
5) calculate difference stream total harmonic distortion, computing formula is:
,
Be the root mean square value of difference stream,
DC component for difference stream.
6) when system's generation disturbance, as the non-latching differential protection of time difference method, sudden change amount ratio differential condition satisfy (
,
),
Condition satisfies, and satisfies simultaneously
Or
, then open differential relay, otherwise locking differential relay.